Fire-Resistant Glass
Integrity and insulating fire glass supplied and fitted into tested frames.
Learn more →For Lowestoft buildings, we supply, replace and check insulated fire glass wherever the fire strategy depends on it, working to the tested system rather than the glass alone.
Tell us what you need. We reply with next steps and a guide price.
EI glass is the choice where people need to pass close to the glass during a fire, where combustible materials sit near it, or where building guidance would otherwise restrict glazing. We supply and fit EI 30 to EI 120 glass in tested frames, internally and externally.
Some EI products are internal only. External use needs a product and edge seal approved for UV and weather.
EI testing limits the average temperature rise on the unexposed face to 140°C and any single point to 180°C, which is why people can pass it.
When heated, the interlayers turn opaque and expand, forming an insulating shield. After a fire the glass will need replacing.
Building work in England is covered by the Building Regulations 2010, with fire safety guidance in Approved Document B and impact safety guidance for glazing in Approved Document K.
Once a building is in use, the Regulatory Reform (Fire Safety) Order 2005 requires the responsible person to maintain fire safety measures, including fire-resisting glazing. The Fire Safety (England) Regulations 2022 add duties for multi-occupied residential buildings, including fire door checks in buildings over 11 metres.
In higher-risk buildings, broadly 18 metres or seven storeys with two or more homes, the Building Safety Regulator is the building control authority. England is also phasing out BS 476 references from Approved Document B, with the remaining fire-resistance references due to go in September 2029.
Our Suffolk coverage takes in Lowestoft (NR32) and the neighbouring towns of Great Yarmouth, Norwich, Stowmarket. Lowestoft lies roughly 62 km from Ipswich, within our Suffolk coverage.
You receive the classification references, glass marks and installation photographs for your fire safety records.
Every quote in Lowestoft identifies the tested system: frame, glass, beads, seals and fixings, within its pane-size limits.
We can phase work in Lowestoft around residents, staff or pupils, with out-of-hours options.
We can survey and quote for care homes, retail and leisure units and other building types in Lowestoft.
Only products approved for external use, usually in a sealed unit with UV protection.
Yes. Once the interlayers have reacted, the glass has done its job and must be replaced.
We can give a guide range from photos and sizes, including a clear photo of any marks on the glass. A fixed price follows a survey.
Building work in Lowestoft follows the Building Regulations 2010 and Approved Document B, and occupied buildings are covered by the Regulatory Reform (Fire Safety) Order 2005.
Integrity and insulating fire glass supplied and fitted into tested frames.
Learn more →E and EW glass where flames and hot gases must be stopped.
Learn more →Glazed screens and doors on protected stairs, lobbies and corridors.
Learn more →Butt-jointed fire glass walls with minimal frames.
Learn more →Send the fire strategy extract, inspection report or a few photos of the openings.
A survey in Lowestoft confirms sizes, access, existing evidence and fixing conditions.
You receive a written quote naming the tested system and classification.
Work is completed to the manufacturer's details and documented for your records.
Send sizes, photos of any glass marks or your inspection report and we will come back with the right tested system.