Fire-Resistant Glass
Integrity and insulating fire glass supplied and fitted into tested frames.
Learn more →For Northampton buildings, we supply, replace and check insulated fire glass wherever the fire strategy depends on it, working to the tested system rather than the glass alone.
Tell us what you need. We reply with next steps and a guide price.
EI glass is the choice where people need to pass close to the glass during a fire, where combustible materials sit near it, or where building guidance would otherwise restrict glazing. We supply and fit EI 30 to EI 120 glass in tested frames, internally and externally.
EI testing limits the average temperature rise on the unexposed face to 140°C and any single point to 180°C, which is why people can pass it.
When heated, the interlayers turn opaque and expand, forming an insulating shield. After a fire the glass will need replacing.
Insulating fire glass should be stored dry, upright and away from direct sun before fitting.
Coverage around Northampton includes the NN1, NN2, NN5, NN3, NN4 districts and nearby Wellingborough, Daventry, Rushden. Northampton is the largest town in our Northamptonshire coverage.
We can phase work in Northampton around residents, staff or pupils, with out-of-hours options.
You receive the classification references, glass marks and installation photographs for your fire safety records.
Designs follow the building and fire safety rules that apply in England, not a one-size-fits-all approach.
Building work in England is covered by the Building Regulations 2010, with fire safety guidance in Approved Document B and impact safety guidance for glazing in Approved Document K.
Once a building is in use, the Regulatory Reform (Fire Safety) Order 2005 requires the responsible person to maintain fire safety measures, including fire-resisting glazing. The Fire Safety (England) Regulations 2022 add duties for multi-occupied residential buildings, including fire door checks in buildings over 11 metres.
We can survey and quote for public buildings, retail and leisure units and other building types in Northampton.
Only products approved for external use, usually in a sealed unit with UV protection.
The glazing system kept fire on one side (integrity) and limited the temperature rise on the other side (insulation) for at least 60 minutes in a standard fire test.
We can give a guide range from photos and sizes, including a clear photo of any marks on the glass. A fixed price follows a survey.
Yes. We plan phasing, out-of-hours work and temporary protection so the building can stay in use where the fire strategy allows.
Integrity and insulating fire glass supplied and fitted into tested frames.
Learn more →E and EW glass where flames and hot gases must be stopped.
Learn more →Glazed screens and doors on protected stairs, lobbies and corridors.
Learn more →Butt-jointed fire glass walls with minimal frames.
Learn more →Send the fire strategy extract, inspection report or a few photos of the openings.
We visit Northampton to measure, record existing marks and check the frames and substrate.
We set out the system, glass, evidence and programme, with a fixed price.
Installation to the system details, then a handover pack with photographs and evidence.
Send sizes, photos of any glass marks or your inspection report and we will come back with the right tested system.